NATIONAL STANDARDS

TCVN 4451:2012

DWELLINGS – BASIC PRINCIPLES FOR DESIGN

Foreword

The TCVN 4451:2012 replaces the TCVN 4451:1987.

The TCVN 4451:2012 is carried over from the TCVN 4451:1987 in accordance with Clause 1 Article 69 of the Law on Technical Standards and Regulations and Point b) Clause 1 Article 6 of Decree No. 127/2007/ND-CP dated August 1, 2007 of the Government elaborating the Law on Technical Standards and Regulations.

The TCVN 4451:2012 is compiled by Vietnam Institute of Architecture, Urban and Rural Planning, proposed by the Ministry of Construction, appraised by the Directorate for Standards, Metrology, and Quality, and published by the Ministry of Science and Technology.

 

DWELLINGS – BASIC PRINCIPLES FOR DESIGN

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

1.1. This Standard applies to design or renovation of apartment buildings (flats), dorms built in cities, towns, city-level towns, or housing complex of agencies, industrial workshops, and schools.

NOTE: Flats of apartment buildings, dorms are hereinafter referred to as “dwellings”.

1.2. This Standard may be applied to old dwellings undergoing repair and under management of the Government, private dwellings built on plots located in cities.

1.3 Design and construction of dwellings in farm dwellings, forestry dwellings shall conform to regulations pertaining to living area, hygiene, and safety under this document. Area of auxiliary structures may adhere to specific regulations depending on local demands.

2. Referencing document

The following referencing document is necessary for the application of this Standard. If a reference document is mentioned together with its publishing year, only the referenced edition shall prevail. If a reference document is not mentioned together with its publishing year, the latest version and all its amendments and revisions (if any) shall prevail.

TCVN 2622, Fire prevention and firefighting for buildings and constructions. Design requirements;

TCVN 4474, Internal drainage - Design standards;

TCVN 4513, Internal water supply - Design standards;

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

TCVN 5687:2010, Ventilation - Air conditioning - Design standards;

TCVN 6772:2000, Water quality. Domestic wastewater. Limit contamination;

TCVN 9210:2012, High-storey dwellings. Design standards;

TCVN 9385:20121), Protection of structures against lightning - Guide for design, inspection and maintenance;

TCVN 9386-1-20121), Design of earthquake-resistant structures;

TCXD 16:19862), Artificial lighting in civil constructions;

TCXD 29:19912), Natural lighting in civil constructions - Design standards;

TCXDVN 377:20062), Central heating systems in dwellings - Design standards;

TCXDVN 387:20062), Central heating systems in dwellings - Construction and commissioning standards.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

In this Standard, the following definitions are used:

3.1. Flat

Refers to living space of a household, a person, or a group of people, satisfies living demands of a family, a group, and each member.

3.2. Apartment building

Refers to a building of at least two storeys with walkways, staircases, and infrastructures for common use by multiple households, individuals.

3.3. Above-ground storey

Refers to a storey whose floor plane is at or higher than ground level of the building according to approved planning.

3.4. Basement

Refers to a storey with more than half of its height below ground level of the building according to approved planning.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

Refers to a storey with half of its height located above or at ground level according to approved planning.

3.6. Attic

Refers to a storey located in the space directly beneath the pitched roof where a part or the entire vertical surface of the storey is created by roof pitches or gables while surrounding walls (if any) are not taller than 1,5 m from the floor.

3.7. Storey height

Refers to the distance from a floor to the floor of the next storey.

3.8. Clear height

Refers to the distance from a finished floor to the underside of load-bearing structures or finished ceiling.

3.9. Dwelling unit

Refers to rooms in a flat used as is or incorporated with other functions. Consists of sleeping units, common rooms, living rooms, study rooms, dining rooms, etc.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

4.1. Dwellings shall be designed depending on classifications under regulations on classifications of civil construction [1].

4.2. Dwelling design shall guarantee rigidity, safety, convenience, conform to climate, natural conditions, traditions, customs, satisfy life and health safety requirements [2], ensure accessibility for people with disability as per the law.

4.3. If mechanical floor is located below floor of the first storey or the ground floor (in the basement), clear height of the mechanical floor shall not be lower than 1,6 m and mechanical floor shall lead directly outside via doors or wall openings with protectives of minimum dimensions of 0,6 m x 0,6 m.

4.4. If height of semi-basements, attics, and above-ground storeys from ground elevation to finished ceiling is not lower than 2 m, such storeys shall be considered storeys of the building.

NOTE: Ground elevation according to approved planning refers to kerb height and is considered grade plane for the purpose of calculating permissible building height.

4.5. Design of installation locations of air-conditioners and drying racks shall not affect vertical architecture of the building and environmental hygiene. Placement of air-conditioners shall be consistent in terms of location and sizes so as to maintain aesthetic.

4.6. Depending on practical demands, garbage collection rooms on storeys or garbage chutes shall be installed.

4.7. Building façade shall not use color or materials that affect vision or health of people. Ensure security, noise, visibility, scenery, and environmental hygiene requirements.

4.8. Advertising panels attached to apartment buildings shall conform to relevant regulations on advertising.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

4.10. Methods for determining block coefficient and plan coefficient of dwellings shall be identified in accordance with Appendix B hereof.

4.11. Design of flats and dorms shall also adhere to TCVN 4450 and TCVN 9201:2012 in addition to this document.

5. Construction plot and general premise planning requirements

5.1. Dwelling construction plots shall satisfy basic principles below:

- Conform to approved construction planning;

- Consist of unified technical infrastructure and social infrastructure satisfying current and future development requirements;

- Not be located in areas where construction activities are prohibited; protective corridors of traffic, irrigation, embankment, energy structures, historical - cultural heritages, and protective zones of other structures as per the law; areas prone to landslide, inundation, contaminated by industrial waste, landfills, cemeteries.

- Ensure fire safety and environmental hygiene.

5.2. Design of dwellings shall take into account flexible use capability and, depending on structure of flats, position on construction plots, architectural space, conform to urban construction requirements [3].

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

- Flats with 2 and 3 rooms: a minimum of 1 room;

- Flats with at least 4 rooms: a minimum of 2 rooms;

Tenements (dorms): a minimum of 40% of dwelling units facing the outside.

NOTE:

1) Direction of facing wind is determined by natural climate parameters in construction [4].

2) In respect of dwelling units facing in appropriate direction, protective solutions shall be required.

6. Architectural design requirements

6.1. Floor elevation shall be at least 0,15 m above kerb height at the entrance.

6.2. Dwelling units shall be located on above-ground storeys. If dwellings are built close to property line, floor elevation of dwelling units shall be at least 0,5 m above kerb height.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

- 30 m2 in case of social housing;

- 45 m2 in case of residential real estates.

6.4. Minimum living area standards in dorms for students and learners of universities, colleges, intermediate professional education, and vocational education and training institutions shall be 4 m2/person.

6.5. Dwelling units in dorms may be incorporated with other rooms such as lobbies, kitchens, restrooms.

6..6 Dorms may facilitate the same kitchens or restrooms for several dwelling units and up to 25 people. Public rooms serving cultural, study, sports, rest, dining, healthcare, administration purposes are required. Composition and area of rooms serving public purposes shall conform to design tasks.

6.7. Depending on occupancy and volume requirements of dwelling units in flats and dorms, height and width shall be designed accordingly.

- Minimum storey height shall be 3,0 m;

- Minimum clear height of rooms shall be 2,7 m;

- Minimum clear height of rooms in attics shall be 1,5 m;

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

6.8. Minimum clear height of auxiliary rooms shall be 2,4 m.

6.9. Height of mechanical floor shall be determined on a case-by-case basis depending on the type of equipment and system therein and operating conditions.

6.10. Maximum depth of dwelling units measured in the direction in which natural light enters the room shall be 6,0 m and twice the width of the dwelling units.

When necessary and for the purpose of increasing module dimensions, depth may be increased by no more than 5%.

6.11. Washing rooms, showers, toilets of upper storeys shall not be directly above kitchens, pantries, and food preparation places in the lower storeys.

6.12. Floors in dwellings shall be soundproofed.

6.13. Number of treads (a flight of stairs) shall not be lower than 3 nor greater than 18.

6.14. Minimum width of corridors between stairs or between stairs and beginning of the corridors shall be:

- 1,4 m if the corridor is up to 40 m in length;

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

6.15. Stairs and intermediate landings shall be fitted with enclosing structures and guardrails. In respect of dwellings for senile people and people with disabilities, wall-side guardrails shall be required.

6.16. Balconies and loggias of buildings of at least 3 storeys shall be of non-combustible materials.

6.17. Loggias and balconies shall not be fitted with glass to serve other purposes.

6.18. Dwellings of more than 6 storeys shall be fitted with elevators. Quantity and parameters of elevators shall be calculated in accordance with selected design solutions.

6.19. Width of elevator lobbies shall be:

- 1,2 m in case of passenger elevators of a load capacity of 400 kg;

- 1,6 m in case of passenger elevators of a load capacity of 630 kg and elevator car of a dimension of (2 100 mm x 1 100 mm);

- 2,1 m in case of elevator car of a dimension of (1 100 mm x 2 100 mm).

NOTE: Dimensions of elevator car are defined as width x depth.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

6.21. If dwellings face strips or city squares, retailers, supermarkets, public food vendors, stores, shops, residential complex management, sports centers below 150 m2, public rooms can be located on the first storey (the ground floor) or basements and semi-basements. In his case, fire safety, soundproofing, and odorproof requirements shall be met in form of appropriate technical solutions. If stores or supermarkets are located in or adjacent to dwellings, entrance to the dwellings shall not be shared with goods loading entrance.

6.22. Dwellings must not contain:

- Pump stations and boilers;

- Electrical substations in or adjacent to buildings;

- Automatic telephone broadcasting stations, other than telephone broadcasting stations serving buildings;

- Headquarters of administrative authorities of all levels;

- Clinics, other than those for gynecology and dental health;

- Dining rooms and cafeterias of more than 50 seats;

- Public restrooms;

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

- Stores of construction materials, chemicals, general items that cause environmental contamination around dwellings;

- Stores selling combustible, explosive commodities;

- Public showers, saunas, chemical washing and bleaching facilities (other than item reception areas and self-serving washing facilities).

6.23. Spaces below dwelling units shall not accommodate:

- Water heaters of hot water supply systems;

- Cold rooms of industrial workshops specializing in business activities and public service.

6.24. Design of dwellings in areas prone to earthquake shall conform to the TCVN 9386-1-2012.

7. Technical system requirements

7.1. Water supply and drainage system design requirements

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

7.1.2. Distribution network of internal water supply pipes shall be placed behind walls or in technical ducts. Valves placed in trenches or technical ducts shall be accompanied by ports for inspection, management, and repair.

7.1.3. Water supply and drainage pipes shall not be installed uncovered below ceilings of rooms.

7.1.4. Wastewater treatment system shall be designed to meet wastewater quality under TCVN 6772:2000 prior to discharging wastewater into area drainage system.

7.1.5. Rooftop rainwater drainage system shall be designed so as to drain rainwater in all weather conditions. Rainwater downpipes must not leak, must be positioned in a way that does not affect architecture and aesthetic, and must be connected to building drainage system.

7.2. Ventilation and air-conditioning system design requirements

7.2.1. Natural ventilation shall be prioritized for dwelling units. Natural ventilation serving dwelling units shall not reach said welling units through kitchens, washing areas, showers, toilets, storage units. Design of ventilation and air-conditioning system shall conform to TCVN 5687:2010.

7.2.2. Toilets and showers shall receive mechanical ventilation in absence of natural ventilation.

7.2.3. Air-conditioners, gas and condenser outlets shall be installed at a position that does not affect other flats, aesthetic, and environmental hygiene.

7.3. Electrical lighting and electric appliance system design requirements

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

7.3.2. Natural lighting shall be prioritized in dwelling units, kitchens, sanitary areas, lobbies, stairs, common corridors, public rooms in dorms. Direct natural lighting is not required in showers, washing areas, toilets, storage units.

7.3.3. Ratio of area of light-transmitting openings in dwelling units and kitchens to floor area of these rooms shall not be greater than 1:5 and lower than 1:8.

7.3.4. Area of light-transmitting openings shall be calculated in accordance with Appendix C.

7.3.5. If lighting is facilitated via openings on exterior walls from gables, common corridor shall be 24 m in length and gables shall be 48 m in length.

If corridor length is higher than the aforementioned values, additional natural lighting shall be facilitated in form of light-transmitting compartments. Two light-transmitting compartments shall not be more than 24 m apart. A light-transmitting compartment shall not more than 30 m away from a light-transmitting opening at the end of the corridor.

If the corridor is below 10 m in length, lighting can be facilitated via stairwells or doors of rooms located along the corridor.

NOTE:

1) Width of light-transmitting openings shall be greater than 1/2 of depth thereof from exterior wall to the side of the corridor.

2) If additional lighting is facilitated by windows of stairwells, ratio of floor area of the stairwells shall be greater than 1/6.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

7.3.7. Lighting systems in flats shall be protected by circuit breakers. Minimum quantity of sockets in rooms shall be 2 sockets. Sockets and junction boxes in showers and kitchens shall be fitted with circuit breakers and located at appropriate height. For safety purposes, all switches and sockets shall be protected by grounded circuit breakers.

7.3.8. Electricity meters shall be installed for each flat. Electricity meters shall be installed for each dorm room or each dorm block.

7.3.9. Lightning protection system shall be designed in accordance with TCVN 9385:2012.

7.4. Communication and telecommunication system design requirements

7.4.1. Design and installation of communication, telecommunication, broadcasting, television systems of dwellings shall ensure safety and convenience in operation, use, connection to service systems of service providers, replacement and repair capability, and separation distance to other technical ducts.

7.4.2. Design and installation of communication, telecommunication, broadcasting, television systems shall conform to relevant regulations.

7.4.3. Cables of communication and television system shall be placed behind walls. A junction box shall be located on each storey.

7.4.4. Radio broadcasting and television network from distribution panels to flats shall travel behind walls in technical ducts; lightning rods shall be protected by lightning protection measures.

Antennas, satellite discs for radio and television signals are allowed on roofs at positions that are allowed by urban authorities and guarantee safety and aesthetic. If necessary, television signal transmitters and receivers are allowed in attics.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

7.5.1. If gas supply system is required in dwellings, the installation shall conform to the TCXDVN 377:2006 and TCXDVN 387:2006.

7.5.2. Design and installation of gas supply system shall satisfy technical specifications regarding pipelines, brackets, measuring instruments, safety equipment, regulations, installation space, and anti-corrosive measures for equipment and pipes.

7.5.3. Main supply pipes and standpipes shall not cross sleeping units, showers, toilets, or garbage storage units.

7.5.4. Kitchens where combustible gas is used shall be fitted with smoke outlets. Kitchen volume shall be sufficient for air during natural combustion.

8. Fire prevention requirements

8.1. Dwellings shall not exceed any limit pertaining to fire resistance category, number of storey, length, construction area under Schedule 1.

Schedule 1 - Fire resistance category, storey, length, construction area limits

Fire resistance category

Storey

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

m

Maximum construction area

m2

With fire walls

Without fire walls

With fire walls

Without fire walls

I-II

No requirement

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

110

No requirement

2 200

III

1 to 5

No requirement

90

No requirement

1 800

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

1

140

70

2 800

1 400

2

100

50

2 000

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

V

1

100

50

2 000

1 000

2

80

40

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

800

NOTE: Point-access dwellings with fire resistance categories I and II where load-bearing structure of the roofs are non-combustible, fire walls shall not be required.

8.2. Maximum distance from doors of dwelling units to stairwells or the nearest exit discharges is specified under Schedule 2.

Schedule 2 - Maximum distance from doors of dwelling units to stairwells or the nearest exit discharges

All dimensions in meter

Fire resistance category

Maximum permissible distance

From rooms between two walkways or two stairwells

From rooms entering dead-end single-loaded corridors

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

40

25

II

40

25

III

30

20

IV

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

15

V

20

10

8.3. Total width of stairs, walkways on means of egress of dwellings, dependent on number of occupants on the most crowded storey other than the first storey, shall be:

- In respect of two-storey dwellings: 1,00 m in width for 125 occupants;

- In respect of three-storey dwellings or higher: 1,00 m in width for 100 occupants;

- If the number of occupants on the most crowded storey is below 125 occupants (in case of two-storey dwellings) or below 100 occupants (in case of three-storey dwellings or higher), the total width shall equal 0,9 m.

8.4 Width of each stringer on means of egress shall be equal to or greater than minimum width of stairs. Slope degree shall be lower than the maximum degree in Schedule 3.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

8.6. In addition, dwelling design shall also conform to regulations on fire safety of buildings and constructions [5] and TCVN 2622.

·Waiting for server...

Type of stairs

Minimum width

m

Maximum slope

1. Primary stairs

a) In two-storey dwellings

 

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

 

1 : 1,5

b) In three-storey dwellings or higher

1,00

1 : 1,75

c) With bicycle loading ramps

-

1 : 2,5

2. Secondary stairs

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

 

a) To basements, non-habitable wallsides

0,90

1 : 1,5

b) To attics

0,09

1 : 1,25

c) Within apartment buildings

0,90

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

NOTE:

1) Width of a flight of stairs refers to the clear dimension between the wall and closed stringers or between two walls or two closed stringers.

2) If width of a flight of stairs is at the lowest value, guardrails shall be located on the outermost side of the flight of stairs.

3) Width of intermediate landings and landings shall not be lower than 1,2 m in respect of regular stairs. Width of intermediate landings and landings shall not be lower than 2,1 m in respect of stairs with bicycle, motorbike loading ramps.

4) Bicycle loading ramps shall not be included in width of flight of stairs. Design of vehicle loading ramps shall ensure safety during emergency evacuation.

5) Slope of stairs shall be calculated by ratio of height to total run of the stairs.

8.7. Minimum clear width of exit accesses is specified under Schedule 4.

Schedule 4 - Minimum clear width of means of egress

All dimensions in meter

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

Minimum width

1. Walkway

1,00

2. Corridor

1,40

3. Door

0,80

4. Stringer

1,05

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

1) If length of a straight section of corridor is not higher than 40 m, width of the corridor may be reduced to 1,2 m.

2) Walkways in flats may be reduced to 0,9 m.

3) Doors on means of egress shall not be smaller than 2,0 m.

 

Appendix A

 (regulation)

Area distribution in dwellings

A.1 Usable area of each flat means total living area and separate area for auxiliary purposes. In respect of multi-storey and multi-unit dwellings, usable area of each flat means area distinct to each flat plus area under common ownership shared by multiple dwelling units, proportionate to living area of each flat.

A.2 Area of rooms and usable sections shall be calculated in proportion to carpet area (other than thickness of walls, partitions, pillars, plaster layers but including thickness of baseboard materials).

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

NOTE: Garbage chutes, chimneys, vents, power tubes, water pipes, and other technical pipes placed in rooms or other sections shall not be included in area of said rooms and sections.

A.3 Usable area in dwellings means total area of dwelling units and auxiliary rooms and is calculated as follows:

a) Living area means total area of primary rooms serving accommodation purposes, including:

- Dwelling units (bedrooms, living rooms, work rooms, playrooms) in flats;

- Dwelling units, bedrooms in dorms;

- Wall cabinets, wardrobes, and cabinets opening towards the inside of dwelling units;

- Area of the underside of stairs in dwelling units of flats (if height from the floor to the underside of stairs is lower than 1,6 m, this area is not included).

b) Auxiliary area: means total area of auxiliary rooms or sections below:

- Guestrooms, living rooms, administration rooms in dorms;

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

- Showers, washing rooms, toilets, walkways in rooms in dwellings with shared toilet;

- Storage units;

- Half of loggia area;

- 0,3 times of balcony and porch area;

- 0,35 times of courtyard area;

- Corridors and walkways of flats or dwelling units;

- Vestibules, anterooms, etc. serving a single flat or several dwelling units;

- Walkways, entrance, anterooms of shared kitchens, washing areas, showers, toilets;

- Wardrobes, and cabinets opening towards the inside of auxiliary sections or rooms.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

A.4 Total usable area of rooms in dorms shall be determined by total area of dwelling units, auxiliary rooms, common rooms, loggias, balconies, porches. Where loggias, balconies, and porches are calculated in accordance with A.3b).

A.5 The following area is not included in total dwelling area: basement area serving ventilation, attics, attics fitted with mechanical system, mechanical floor, technical system outside of flats, staircase vestibules, elevator shafts, outdoor staircases.

A.6 Dwelling area is calculated by adding up area of all storeys limited by the inside of exterior walls, balcony and loggia area. Area of staircases and elevator shafts shall be included in area of said storeys.

A.7 Area of rooms in dwellings shall be determined by dimensions limited by walls (not including baseboards). Area of attics shall be calculated as follows:

- Ceiling height shall be 1,5 m if the ceiling is pitched at a 30o angle;

- Ceiling height shall be 1,1 m if the ceiling is pitched at a 45o angle;

- Ceiling height shall be 0,5 m if the ceiling is pitched at a 60o angle or higher;

A.8 Traffic area means total area of common sections of flats or dwelling units used for moving around inside dwellings. Area of sections below is included in traffic area:

a) Staircases, including intermediate landings and landings;

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

c) Vestibules, lobbies;

d) Outdoor staircases;

A.9 Structural area means total area of walls, pillars on plan view. Area of sections below is included in structural area:

a) Load-bearing and non-load bearing walls, partitions, pillars;

b) Door thresholds, window sills;

c) Chimneys, vents, power tubes, water pipes, other technical ducts, including the inside and the casing;

d) Wall niches, empty spaces between two rooms (without doors) with width below 1,5 m and height below 1,9 m.

NOTE: Structural area is determined by subtracting living area, auxiliary area, and traffic area from floor area of a storey. in case of the first storey (ground floor), this area is construction area less living area, auxiliary area, and traffic area.

A.10 Other area means total area of rooms or sections not serving accommodation purposes such as: dining area, retailers, parking spaces, hairdresser’s, public washing rooms, etc.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

NOTE: Construction area equals the sum of living area, auxiliary area, traffic area, structural area, and other area of the first storey.

A.12 Building volume equals the sum of building volume at grade plane (for above-ground sections) and below grade plane (for underground sections).

A.13 Building volume of a dwelling, a storey, a flat means the product of construction area of the dwelling, floor area of a storey or a flat and height of the dwelling, storey, and flat. Height shall be calculated in accordance with 6.8 and 6.9 hereof.

A.14 Kitchens and sanitary areas that are shared or located outdoors shall not be included in dwelling area; area of these auxiliary sections shall be calculated independently.

A.15 Private area and common area in apartment buildings.

a) Apartment buildings mean dwellings with at least two storeys, with walkways, staircases, and infrastructures shared by multiple households and individuals. Apartment buildings consist of private sections of each household, individual, and common sections shared by all households and individuals therein.

b) Private sections in apartment building include:

- Area inside flats, including balconies and loggias associated with the flats;

- Other area in apartment buildings recognized as private area as per the law;

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

c) Common sections in apartment buildings include:

- Remaining area in apartment buildings other than those in Clause 2 of A.15;

- Space and load-bearing elements, technical equipment for common use in apartment buildings, including frames, pillars, load-bearing walls, exterior walls, separating walls, floors, ceilings, rooftops, corridors, staircases, elevators, means of egress, garbage chutes, technical boxes, parking spaces, power supply system, water supply system, gas supply system communication, radio, television system, water drainage system, septic tank, lightning rods, fire safety, and other sections not owned by any single flat;

- Outdoor technical infrastructures connected to the apartment buildings.

 

Appendix B

 (regulation)

Methods for determining block coefficient of dwellings

B.1 Dwelling design shall include calculation of coefficients: K, K1, K2.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

a) Coefficient K means ratio of living area to construction area or living area of flat to floor area of the flat.

K =

Living area

(1)

Construction area (floor area)

b) Coefficient K1 means ratio of living area to usable area of a dwelling or a flat:

K1 =

Living area

(2)

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

c) Coefficient K2 means ratio of building volume of a dwelling (or a flat) to living area:

K2 =

Building volume of dwelling (flat)

(3)

Living area

d) Coefficients may vary:

K = 0,40 to 0,45

K1 = 0,48 to 0,55

K2 = 0,50 to 6,50

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

Appendix C

 (Reference)

Area and types of light-transmitting openings

C.1 Area of light-transmitting openings shall be calculated as follows:

a) Equal to area of empty walls for window installation in case of windows;

b) Equal to area of light-transmitting glass section including mullions in case of doors;

c) Equal to clear space of perforations if perforation thickness does not exceed 10 cm. Or 2/3 of clear space of perforations if perforation thickness exceeds 10 cm.

C.2 The following openings are included in light-transmitting area:

a) Windows opening towards the outside, loggias, balconies, or single-loaded corridors;

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

C.3 The following openings are not included in light-transmitting area:

a) Windows and doors leading to center corridors, single-loaded corridors;

b) Doorstops, loggias, empty spaces for ventilation;

c) Doors between rooms.

 

REFERENCE

 [1] QCVN 03:2009/BXD, National Technical Regulation on Classifications of civil, industrial structures and urban technical infrastructures;

 [2] QCXDVN 05:2008/BXD, National Construction Regulation - Houses and public structures - Life and Health Safety;

 [3] QCXDVN 01:2008/BXD, National Construction Regulation– Construction planning;

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

 [5] QCVN 06:2010/BXD, National Technical Regulations - Fire safety for buildings and structures.

 

Table of contents

Foreword

1 Scope

2 Reference documents

3 Definitions

4 GENERAL PROVISIONS

5 Construction plot and general premise planning requirements

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

7 Technical system requirements

7.1. Water supply and drainage system design requirements

7.2 Ventilation and air-conditioning system design requirements

7.3 Electrical lighting and electric appliance system design requirements

7.4 Communication and telecommunication system design requirements

7.5 Gas supply system design requirements

8 Fire safety requirements

Appendix A (regulation) Area distribution in dwellings

Appendix B (regulation) Methods for determining block coefficient of dwellings

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

Reference

1) TCVN to be promulgated

2) TCXD and TCXDVN being carried over.

25
Tiện ích dành riêng cho tài khoản TVPL Basic và TVPL Pro
Tiện ích dành riêng cho tài khoản TVPL Basic và TVPL Pro
Tiện ích dành riêng cho tài khoản TVPL Basic và TVPL Pro
Tải về National Standards TCVN 4451:2012 for Dwellings - Basic principles for design
Tải văn bản gốc National Standards TCVN 4451:2012 for Dwellings - Basic principles for design

Bậc chịu lửa

Số tầng

Chiều dài giới hạn lớn nhất của ngôi nhà

m

Diện tích xây dựng lớn nhất cho phép

m2

Có tường ngăn cháy

Không có tường ngăn cháy

Có tường ngăn cháy

Không có tường ngăn cháy

I-II

Không quy định

Không quy định

110

Không quy định

2 200

III

Từ 1 đến 5

Không quy định

90

Không quy định

1 800

IV

1

140

70

2 800

1 400

2

100

50

2 000

1 000

V

1

100

50

2 000

1 000

2

80

40

1 600

800

CHÚ THÍCH: Nhà ở kiểu đơn nguyên với bậc chịu lửa I và II có kết cấu chịu lực của mái không cháy thì cho phép không xây dựng tường ngăn cháy.

8.2. Khoảng cách lớn nhất từ cửa vào của phòng ở tới buồng thang hoặc lối thoát ra ngoài gần nhất được quy định trong Bảng 2.

Bảng 2 – Khoảng cách lớn nhất từ cửa phòng ở tới buồng thang hoặc lối thoát gần nhất

Kích thước tính bằng mét

Bậc chịu lửa

Khoảng cách xa nhất cho phép

Từ những phòng bố trí giữa hai lối đi, hay hai buồng thang

Từ những phòng có lối vào hành lang bên cụt

I

40

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

II

40

25

III

30

20

IV

25

15

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

20

10

8.3. Chiều rộng tổng cộng của các cầu thang, các đường đi trên lối thoát nạn của ngôi nhà, tính theo số người trong tầng đông nhất, không kể tầng 1 được quy định trong như sau:

- Đối với nhà ở hai tầng: 1,00 m chiều rộng cho 125 người;

- Đối với nhà ở ba tầng trở lên: 1,00 m chiều rộng cho 100 người;

- Khi số lượng ở tầng đông nhất dưới 125 người (đối với nhà 2 tầng) hoặc dưới 100 người (đối với nhà 3 tầng trở lên) thì chiều rộng tổng cộng lấy bằng 0,90 m.

8.4. Chiều rộng mỗi vế thang trên lối thoát nạn phải bảo đảm bằng hoặc lớn hơn chiều rộng nhỏ nhất cầu thang. Độ dốc phải nhỏ hơn độ dốc lớn nhất quy định trong Bảng 3.

8.5. Cần thiết kế hệ thống báo cháy tự động để thông báo cho mọi người biết khi có cháy.

8.6. Ngoài những quy định trên đây, khi thiết kế nhà ở còn phải tuân theo những quy định về an toàn cháy cho nhà và công trình [5] và TCVN 2622.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

Loại cầu thang

Chiều rộng nhỏ nhất

m

Độ dốc lớn nhất

1. Thang chính

a) Trong nhà ở hai tầng

 

0,90

 

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

b) Trong nhà ở trên ba tầng

1,00

1 : 1,75

c) Có vệt dắt xe đạp

-

1 : 2,5

2. Thang phụ

 

 

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

0,90

1 : 1,5

b) Lên tầng áp mái

0,09

1 : 1,25

c) Trong nội bộ căn hộ

0,90

1 : 1,25

CHÚ THÍCH:

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

2) Khi chiều rộng vế thang bằng mức nhỏ nhất thì tay vịn phải để phía ngoài cùng của vế thang.

3) Chiều rộng của chiếu nghỉ, chiếu tới không được nhỏ hơn 1,2 m đối với mọi cầu thang thông thường. Đối với cầu thang có vệt dắt xe đạp, xe máy không được nhỏ hơn 2,1 m.

4) Vệt dắt xe đạp không tính vào chiều rộng của vế thang. Khi thiết kế vệt dắt xe phải tính toán điều kiện an toàn cho thoát nạn khi có sự cố.

5) Độ dốc cầu thang tính bằng tỉ lệ chiều cao trên chiều rộng của bậc.

8.7. Chiều rộng thông thủy nhỏ nhất cho phép của lối thoát nạn được quy định trong Bảng 4.

Bảng 4 – Chiều rộng thông thủy nhỏ nhất của lối thoát nạn

Kích thước tính bằng mét

Loại lối đi

Chiều rộng nhỏ nhất cho phép

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

1,00

2. Hành lang

1,40

3. Cửa đi

0,80

4. Vế thang

1,05

CHÚ THÍCH

1) Khi chiều dài đoạn hành lang thẳng không lớn hơn 40 m thì chiều rộng hành lang được phép giảm đến 1,2 m.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

3) Các cửa đi trên lối thoát nạn không được nhỏ hơn 2,0 m.

 

Phụ lục A

(quy định)

Phân định diện tích trong nhà ở

A.1 Diện tích sử dụng của mỗi căn hộ là tổng diện tích ở và diện tích phụ sử dụng riêng biệt. Đối với nhà ở nhiều căn hộ thì diện tích sử dụng của mỗi căn hộ là diện tích sử dụng riêng biệt của từng căn hộ cộng với phần diện tích phụ dùng chung cho nhiều hộ, được phân bổ theo tỷ lệ với diện tích ở của từng căn hộ.

A.2 Diện tích các phòng, các bộ phận sử dụng đều được tính theo kích thước thông thủy (trừ bề dày tường, vách, cột kể cả lớp trát nhưng không trừ bề dày lớp vật liệu ốp chân tường hay ốp tường).

Diện tích các gian phòng có chiều cao thấp hơn được tính vào tổng diện tích với hệ số 0,7.

CHÚ THÍCH: Các ống rác, ống khói, thông hơi, điện, nước và các đường ống kỹ thuật khác đặt trong phòng hay bộ phận nào thì không tính vào diện tích các gian phòng hay bộ phận đó.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

a) Diện tích ở là tổng diện tích các phòng chính dùng để ở bao gồm:

- Phòng ở (phòng ngủ, phòng sinh hoạt chung, phòng khách, phòng làm việc, giải trí) trong nhà ở căn hộ;

- Phòng ở, phòng ngủ trong nhà ở ký túc xá;

- Các tủ tường, tủ xây, tủ lẩn có cửa mở về phía trong phòng ở;

- Diện tích phần dưới cầu thang bố trí trong các phòng ở của căn hộ (nếu chiều cao từ mặt nền đến mặt dưới cầu thang dưới 1,60 m thì không tính phần diện tích này).

b) Diện tích phụ: là tổng diện tích các phòng phụ hoặc bộ phận sau đây:

- Phòng tiếp khách, sinh hoạt chung, phòng quản lý trong nhà ở ký túc xá;

- Bếp (chỗ đun nấu, rửa, gia công, chuẩn bị) không kể diện tích chiếm chỗ của ống khói, ống rác, ống cấp, thoát nước;

- Phòng tắm rửa, giặt, xí, tiểu và lối đi bên trong các phòng đối với nhà ở thiết kế khu vệ sinh tập trung;

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

- Một nửa diện tích lôgia;

- 0,3 diện tích ban công, thềm;

- 0,35 diện tích sân trời;

- Các hành lang, lối đi của căn hộ hoặc các phòng ở;

- Các tiền sảnh, phòng đệm… sử dụng riêng cho một căn hộ hoặc một vài phòng ở;

- Các lối đi, lối vào, phòng đệm của khu bếp hay khu tắm rửa, giặt, xí, tiểu tập trung;

- Các tủ xây, tủ lẩn của căn hộ có cửa mở về phía trong các bộ phận hay phòng phụ.

CHÚ THÍCH: Trong nhà ở nhiều căn hộ, diện tích phụ dùng chung cho nhiều căn hộ như phòng để xe, phòng sinh hoạt công cộng chung, phòng quản lý hoặc bảo vệ thì không tính vào diện tích trên.

A.4 Tổng diện tích sử dụng các gian phòng trong ký túc xá được xác định bằng tổng diện tích các phòng ở, phòng phụ trợ, phòng phục vụ công cộng, lôgia, ban công, hiên. Trong đó lôgia, ban công, hiên được tính theo quy định ở A. 3 b).

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

A.6 Diện tích nhà ở được tính bằng tổng diện tích các tầng nhà, trong giới hạn mặt bên trong của tường ngoài, với diện tích ban công và lôgia. Diện tích cầu thang, giếng thang máy, được tính vào diện tích tầng nhà của tầng đó.

A.7 Diện tích các gian phòng trong nhà ở được tính theo các kích thước đo giữa các bề mặt ngăn cách của tường và tường ngăn trên sàn nhà (không tính gờ chân tường). Khi xác định diện tích tầng áp mái thì tính như sau:

- Trần áp mái dốc 30o – chiều cao trần lấy 1,5 m;

- Trần áp mái dốc 45o – chiều cao trần lấy 1,1m;

- Trần áp mái dốc 60o trở lên – chiều cao trần lấy 0,5m.

A.8 Diện tích giao thông là tổng diện tích các bộ phận sử dụng chung cho căn hộ hoặc các phòng ở vào việc đi lại trong ngôi nhà. Diện tích các bộ phận sau đây đều tính vào diện tích giao thông:

a) Buồng thang, kể cả chiếu nghỉ, chiếu tới;

b) Hành lang sử dụng chung cho các căn hộ, các phòng ở;

c) Tiền sảnh, sành tầng;

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

A.9 Diện tích kết cấu là tổng số diện tích của tường vách, cột tính trên mặt bằng (mặt cắt bằng). Diện tích các bộ phận sau đây đều tính vào diện tích kết cấu:

a) Tường chịu lực hay không chịu lực, tường ngăn, vách ngăn, cột;

b) Ngưỡng cửa đi, bậu cửa sổ các loại;

c) Các ống khói, các ống thông hơi, ống điện, nước và các ống kỹ thuật khác kể cả phần lòng ống và thành ống;

d) Các hốc tường, các khoảng trống giữa hai phòng (không lắp cửa đi) có chiều rộng nhỏ hơn 1,50m và chiều cao nhỏ hơn 1,90m.

CHÚ THÍCH: Diện tích kết cấu được xác định bằng cách lấy diện tích nền (sàn) của tầng trừ đi các diện tích ở, diện tích phụ, diện tích giao thông của tầng ấy. Nếu là tầng một (tầng trệt) thì chính là diện tích xây dựng trừ đi các diện tích ở, diện tích phụ, diện tích giao thông.

A.10 Diện tích khác là tổng số diện tích của các phòng hay bộ phận không dùng để ở mà chỉ dùng vào các chức năng sử dụng khác của ngôi nhà như: ăn uống, giải khát, cắt tóc, cửa hàng bán lẻ, chỗ để xe, phòng giặt công cộng…

A.11 Diện tích xây dựng là diện tích tính theo kích thước phủ bì của tường ngoài, dãy cột có mái che, cầu thang ngoài nhà, bậc thềm, lối đi, cửa đi, lôgia, sân trời.

CHÚ THÍCH: Diện tích xây dựng bằng tổng diện tích ở, diện tích phụ, diện tích giao thông, diện tích kết cấu và diện tích khác của tầng một.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

A.13 Khối tích xây dựng của ngôi nhà, một tầng nhà, một căn hộ là tích số của diện tích xây dựng của ngôi nhà, diện tích sàn của tầng hoặc căn hộ với chiều cao của ngôi nhà, tầng nhà và từng căn hộ. Chiều cao được tính như quy định tại 6.8 và 6.9 của tiêu chuẩn này.

A.14 Khu bếp và khu vệ sinh tập trung, bố trí ngoài ngôi nhà ở, không tính vào diện tích của nhà ở, diện tích của những công trình phụ này được tính riêng.

A.15 Phần sở hữu riêng và phần sở hữu chung trong nhà chung cư.

a) Nhà chung cư là nhà ở có từ hai tầng trở lên, có lối đi, cầu thang và hệ thống công trình hạ tầng sử dụng chung cho nhiều hộ gia đình, cá nhân. Nhà chung cư có phần sở hữu riêng của từng hộ gia đình, cá nhân và phần sở hữu chung của tất cả các hộ gia đình, cá nhân sử dụng nhà chung cư.

b) Phần sở hữu riêng trong nhà chung cư bao gồm:

- Phần diện tích bên trong căn hộ, bao gồm cả diện tích ban công, lôgia gắn liền với căn hộ đó;

- Phần diện khác trong nhà chung cư được công nhận là sở hữu riêng theo quy định của pháp luật;

- Hệ thống trang thiết bị kỹ thuật sử dụng riêng gắn liền với căn hộ, phần diện tích thuộc sở hữu riêng.

c) Phần sở hữu chung trong nhà chung cư bao gồm:

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

- Không gian và hệ thống kết cấu chịu lực, trang thiết bị kỹ thuật dùng chung trong nhà chung cư, gồm khung, cột, tường chịu lực, tường bao ngôi nhà, tường phân chia các căn hộ, sàn, mái, sân thượng, hành lang, cầu thang bộ, thang máy, đường thoát hiểm, lồng xả rác, hộp kỹ thuật, nơi để xe, hệ thống cấp điện, nước, ga, thông tin liên lạc, phát thanh, truyền hình, thoát nước, bể phốt, thu lôi, cứu hỏa và các phần khác không thuộc sở hữu riêng của căn hộ nào;

- Hệ thống hạ tầng kỹ thuật bên ngoài nhưng được kết nối với nhà chung cư đó.

 

Phụ lục B

(quy định)

Phương pháp xác định hệ số khối mặt bằng của nhà ở

B.1 Khi thiết kế nhà ở phải tính toán hệ số khối: K, K1, K2.

B.2 Hệ số khối mặt bằng K, K1, K2 được xác định như sau:

a) Hệ số mặt bằng K là tỉ số của diện tích ở trên diện tích xây dựng hoặc diện tích ở căn hộ trên diện tích sàn của căn hộ.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

Diện tích ở

(1)

Diện tích xây dựng (sàn)

b) Hệ số mặt bằng K1 là tỉ số của diện tích ở trên diện tích sử dụng của ngôi nhà hoặc căn hộ:

K1 =

Diện tích ở

(2)

Diện tích sử dụng

c) Hệ số khối K2 là tỉ số của khối tích xây dựng của ngôi nhà (căn hộ) trên diện tích ở:

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

Khối tích xây dựng của ngôi nhà (căn hộ)

(3)

Diện tích ở

d) Các hệ số khối, mặt bằng có thể dao động trong các khoảng:

K = 0,40 đến 0,45

K1 = 0,48 đến 0,55

K2 = 0,50 đến 6,50

 

Phụ lục C

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

Diện tích và loại cửa lấy ánh sáng

C.1 Diện tích của cửa lấy ánh sáng được tính như sau:

a) Với cửa sổ lấy bằng khoảng tường trống để lắp cửa;

b) Với cửa đi lấy bằng diện tích của khoảng kính lấy ánh sáng không trừ đố;

c) Với lỗ hoa lấy bằng khoảng trống của lỗ hoa, khi bề dày của lỗ hoa không quá 10 cm. Nếu quá 10 cm thì lấy bằng 2/3 khoảng trống của lỗ hoa.

C.2 Những cửa sau đây được tính vào diện tích lấy ánh sáng:

a) Cửa sổ mở trực tiếp ra ngoài trời, hiên lô gia, ban công hoặc hành lang bên thoáng (không có tường ngoài và cửa sổ);

b) Phần kính của cửa đi khi mở trực tiếp ra hiên, lô gia, ban công hoặc hành lang thoáng.

C.3 Những loại cửa sau đây không tính vào diện tích lấy ánh sáng:

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

b) Cửa hãm, lôgia, lỗ trống dùng để thông hơi;

c) Cửa ngăn cách giữa các phòng.

 

THƯ MỤC TÀI LIỆU THAM KHẢO

[1] QCVN 03:2009/BXD, Quy chuẩn kỹ thuật quốc gia về phân loại, phân cấp công trình xây dựng dân dụng, công nghiệp và hạ tầng kỹ thuật đô thị;

[2] QCXDVN 05:2008/BXD, Quy chuẩn xây dựng Việt Nam – Nhà ở và công trình công cộng – An toàn sinh mạng và sức khỏe;

[3] QCXDVN 01:2008/BXD, Quy chuẩn xây dựng Việt Nam – Quy hoạch xây dựng;

[4] QCXDVN 02:2008/BXD, Quy chuẩn xây dựng Việt Nam – Số liệu điều kiện tự nhiên dùng trong xây dựng – Phần 1;

[5] QCVN 06:2010/BXD, Quy chuẩn kỹ thuật quốc gia về an toàn cháy cho nhà và công trình.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

MỤC LỤC

Lời nói đầu

1 Phạm vi áp dụng

2 Tài liệu viện dẫn

3 Thuật ngữ và định nghĩa

4 Quy định chung

5 Yêu cầu về khu đất xây dựng và quy hoạch tổng mặt bằng

6 Yêu cầu thiết kế kiến trúc

7 Yêu cầu về hệ thống kỹ thuật

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

7.2 Yêu cầu thiết kế hệ thống thông gió, điều hòa không khí

7.3 Yêu cầu thiết kế hệ thống điện chiếu sáng và thiết bị điện

7.4 Yêu cầu thiết kế hệ thống thông tin liên lạc, viễn thông

7.5 Yêu cầu thiết kế hệ thống cung cấp ga, khí đốt

8 Yêu cầu về phòng cháy

Phụ lục A (quy định) Phân định diện tích trong nhà ở

Phụ lục B (quy định) Phương pháp xác định hệ số khối mặt bằng của nhà ở

Phụ lục C (quy định) Diện tích và loại cửa lấy ánh sáng

Thư mục tài liệu tham khảo

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

(2) Các TCXD và TCXDVN đang được chuyển đổi.

Văn bản được hướng dẫn - [0]
[...]
Văn bản được hợp nhất - [0]
[...]
Văn bản bị sửa đổi bổ sung - [0]
[...]
Văn bản bị đính chính - [0]
[...]
Văn bản bị thay thế - [0]
[...]
Văn bản được dẫn chiếu - [0]
[...]
Văn bản được căn cứ - [0]
[...]
Văn bản liên quan ngôn ngữ - [1]
[...]
Văn bản đang xem
National Standards TCVN 4451:2012 for Dwellings - Basic principles for design
Số hiệu: TCVN4451:2012
Loại văn bản: Tiêu chuẩn Việt Nam
Lĩnh vực, ngành: Xây dựng
Nơi ban hành: ***
Người ký: ***
Ngày ban hành: 01/01/2012
Ngày hiệu lực: Đã biết
Ngày đăng: Đã biết
Số công báo: Đã biết
Tình trạng: Đã biết
Văn bản liên quan cùng nội dung - [0]
[...]
Văn bản hướng dẫn - [0]
[...]
Văn bản hợp nhất - [0]
[...]
Văn bản sửa đổi bổ sung - [0]
[...]
Văn bản đính chính - [0]
[...]
Văn bản thay thế - [0]
[...]
[...] Đăng nhập tài khoản TVPL Basic hoặc TVPL Pro để xem toàn bộ lược đồ văn bản