NATIONAL STANDARD

TCVN 6486 : 2008

LIQUEFIED PETROLEUM GAS (LPG) – PRESSURISED STORAGE – REQUIREMENTS FOR DESIGN AND LOCATION OF INSTALLATION

Foreword

TCVN 6486 : 2008 supersedes TCVN 6486 : 1999.

TCVN 6486 : 2008 is jointly compiled by the Technical Committee in charge of TCVN/TC 58 Gas cylinders and Gas Petrolimex Corporation JSC at the request of the Directorate for Standards, Metrology and Quality, and announced by the Ministry of Science and Technology.

 

LIQUEFIED PETROLEUM GAS (LPG) – PRESSURISED STORAGE – REQUIREMENTS FOR DESIGN AND LOCATION OF INSTALLATION

1. Scope  

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

1.2. This standard shall not apply to:

- Storage of LPG for transportation;

- Storage in the course of gas distillation or separation;

- Refrigerated storage.

2. Referenced documents

The following referenced documents are indispensable for the application of this document. For dated referenced documents, the edition cited shall apply. For undated referenced documents, the most recent edition or revision shall apply.

TCVN 5684 Fire safety for petroleum and petroleum products facilities – General requirements.

TCVN 6008 Pressure equipments - Welds - Technical requirements and testing methods.

TCVN 6153 Pressure vessels - Safety engineering requirements of design, construction, manufacture.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

TCVN 6155 Pressure vessels – Safety engineering requirements of erection, use, repair.

TCVN 6156 Pressure vessels – Safety engineering requirements of erection, use, repair – Testing method.

TCVN 7441: 2004 Liquefied Petro gas (LGP) Compounds at Consumption Ends – Requirements in Design, Installation.

3. Terms and definitions

The terms and definitions used in this standard include:

3.1. Design pressure

The pressure to be used in determining the minimum permissible wall thickness of LPG bulk tank so that it is capable of handling the LPG pressure at the maximum operating temperature.

3.2. LPG bulk tank

A container used for storing LPG with a water capacity exceeding or equal to 0.15 m3.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

A tank installed above grade and not covered with sand or earth.

3.2.2. Underground tank

A tank buried below the general grade and covered with sand or earth.

3.2.3. Mounded tank

A tank located above the general grade level and covered with sand or earth.

3.3. LPG system

A system is comprised of a tank and equipment such as pumps, compressors, piping, fittings, shutoff valves, control valves, connectors, etc. required for handling LPG.

3.4. Liquefied petroleum gas (LPG)

A hydrocarbon mixture composed predominantly of butane (C4H10) and propane (C3H8). These components account for at least 95% of the mixture by weight.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

3.5. Separation distance

The minimum distance between buildings or structures which must be kept to ensure the safety in case of LPG leakage or fire, minimize the possibility of damage and prevent gas dispersal.

3.6. Explosible area

The area where the mixture of LPG and air may cause fire or explosion.

3.7. Producer/ supplier

The entity that produces or supplies equipment and relevant services to meet the purchaser’s requirements.

3.8. Fire wall

A wall constructed of brick or concrete or another material with a fire resistance of at least 60 minutes and a height of at least 2m or higher than the top of the tank, and used to protect the tank from the heat radiation by an external fire and prevent the dispersal of LPG vapor to adjacent constructions or external ignition sources if the leakage of LPG occurs.

3.9. Excess-flow valve

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

A shutoff valve incorporating manual or combined means of closing installed to stop the supply of LPG immediately in an emergency.

3.11. Pressure relief valve

A valve designed to protect the LPG system in case of overpressure by mean of automatically discharging LPG to the outside of the system.

4. General requirements

4.1. LPG tanks must be used in compliance with applicable regulations adopted by competent authorities.

4.2. LPG tanks and systems must be designed, manufactured, installed, repaired, inspect, tested and maintained in accordance with national standards, including TCVN 6153, TCVN 6154, TCVN 6155, TCVN 6156 and TCVN 6008, and applicable regulations laid down in relevant technical standards.

5. Requirements for design of aboveground tanks

5.1. General requirements

5.1.1. A LPG bulk tank must be designed for storage of 100% of commercial propane at the highest temperature. The design pressure of the mixture must be selected with a consideration of mixture pressures that may occur in the course of tank operation.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

5.1.3. The selected maximum design temperature is the highest temperature of the product handed by the tank at normal operation plus a temperature differential to ensure that the safety valve does not lift in normal conditions.     

5.1.4. The selected minimum design temperature shall be -20°C, unless a lower temperature of a tank shell or the contents of the tank.    In such case, the lowest temperature shall be selected.

5.1.5. The minimum wall thickness shall include a corrosion allowance of 1 mm if the tank is made of carbon steel.

5.2. Tank connections, fittings and accessories

5.2.1. Any tanks shall have an access hole or inspection pit.  A tank’s access hole shall have an oval or circular shape of at least 400 mm x 300 mm in size or at least 400 mm in diameter respectively.  An inspection pit's size must be suitable for inspecting the inside of the tank.

5.2.2. A tank must be equipped with connectors, fittings and accessories suitable for the use of LPG and conformable with relevant standards.

5.2.3. A tank shall have at least the following appurtenances:   

- Pressure relief valve

- Liquid LPG filling valve

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

- Vapor LPG withdrawal valve

- Blowdown valve

- Liquid LPG level gauge

- Pressure gauge

5.2.3.1. Pressure relief valve

The pressure relief valve shall be installed to provide direct connection to the vapor LPG space of the tank and removed for regular inspection and testing by adopting suitable methods. The size of a pressure relief valve must correspond to the outside surface area of the tank in conformity with provisions laid down in TCVN 7441: 2004.
5.2.3.2. Liquid LPG filling valves

At least a check valve and a shut-off valve must be installed on the liquid LPG fill line.  A valve installed on a pipe joint with a nominal diameter of greater than 50 mm must be made of cast steel and be a ball valve with a working pressure at least equal to the Design Pressure of the piping system.

5.2.3.3. Liquid and vapor LPG withdrawal valves

An excess-flow valve and a manual shutoff valve or emergency shut-off valve must be installed on pipe joints at the outlet of the LPG withdrawal line. A ball valve installed on a pipe joint with a nominal diameter of greater than 50 mm must be made of cast steel. The emergency shut-off valve must be the one closed automatically by the operation of a heat-sensing metal cap or manually from a remote position, ensuring separation distance, by mechanical means or compressed air in case of emergency.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

The blowdown pit of a tank must be located at the lowest portion of the section occupied by liquid; two block valves must be installed on the drain pipe outside the tank with the aims of preventing leakage; the minimum distance between these two valves shall be 500 mm so that the spilled liquid shall not freeze and make the valve obstructed.

5.2.3.5. Metering and gauging equipment

Each tank shall be provided with at least a liquid-level gauge with a range of levels indicating the tank capacity, and a pressure gauge which should be connected to the vapor LPG space.  The hole of the gauge used to measure the level of liquid LPG vented to atmosphere must be at least 1.5 mm in diameter. A temperature gauge, when fitted, must be installed in load-bearing pocket.

5.3. Tank supports

5.3.1. Tank supports must meet its design standards and be weld to saddle or V-shape plates already weld on the tank shell.  

5.3.2. The design of supports for tanks shall include provisions for expansion and contraction of the tank due to pressure and temperature. For tanks of less than 50 m3 capacity, the anchored structure may be employed to adjust the expansion level.

5.3.3. The design of the tank support must ensure that after installation, the tank has a downward slope of from 1 : 100 to 1 : 400 towards the tank discharge hole.

5.3.4. Tank foundations and supports must be capable of bearing loads when the tank space is completely filled with water.

5.3.5. Tank supports shall be designed so that the space underneath the tank is sufficient to install pipe lines and ensure safe operation and maintenance of equipment installed under the tank.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

5.4. Requirements for earthing

5.4.1. The lightning rod is not required but the LPG tank must be earthed with earth resistance of not exceeding 10 W.

5.4.2. Each tank is required to have at least two metal wires weld to the earthing system for the purposes of protecting the tank from lightning and static electricity.  Earth resistance of this system shall not exceed 10 W.

5.4.3. LPG tankers must be connected with the safety earthing system at the LPG loading position.

5.4.4. The safety earthing system must have an earth resistance of not exceeding 4 W. All of dead parts of electrical equipment and pumps must be connected to the safety earthing system.

This earthing system must be located at least 5 m far away from the earthing system for protection from direct lightning strike.

If a safety earthing system is connected to the earthing system for protection from direct lightning strike, total earth resistance shall not exceed 1 W.

6. Tank location

6.1. LPG tanks must be located outdoor and outside the house or building, and not located on the top or balcony or in the basement of a building.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

The LPG tank must be located at least 1.5 m from the top view of the overhead power lines that are less than 1 kV. This required distance may rise to 7.5 m if the overhead power lines are over 1 kV.

6.3. If a LPG tank storage area is located adjoining doorways to the line of property occupied by hospitals, schools, shopping malls, etc., it must be protected by an enclosure with an open-type fence of at least 1.8 m high and located at least 1.5 m from a tank. There shall be at least two means of access to and exit from the fenced enclosure.  This is an outward opening lockable gate not less than 1 m wide.

6.4. A tank storage area shall be provided with appropriate safety precaution signs which must be kept in a legible condition such as danger signs, instructions for fire protection and alarming, and telephone number of fire agencies.

6.5. Pressure relief valves must be maintained in good conditions.   The relief valve discharge shall be located at the uppermost point of the tank, well-ventilated and directed upward. Any pressure relief valves installed on LPG piping system, LPG cylinders and LPG tanks shall not directed toward any tank, LPG piping and operators.  

6.6. Tanks must not be stacked one above the other. Aboveground tanks must be securely supported.  Tank supports must be flat and capable of supporting the weight of the tank filled with water.

6.7. The ground under a tank used to store LPG shall be graded to prevent the accumulation of any LPG liquid leaked from the tank.

6.8. Where the fire water system is applied, the drainage must be a consideration when determining the installation of this fire water system.  

6.9. Tanks should not be located in areas where there is a risk of flooding. Where an underground or mounded tank is located in an area where there is large volume of groundwater, it must be firmly anchored to prevent floating.

6.10. Minimum separation distances from storage tanks to nearest structures, buildings or office buildings and those between tanks are provided for in the following Table 1.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

Water capacity per tank (m3)

Minimum separation distances (m)

 

 

Underground or mounded tank

Aboveground tank

Between tanks

<0.5

3

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

0

  0.5 to 1.0

3

3

0

1.0 to 1.9

3

3

1

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

3

7.6

1

 7.6 to 114

15

15

1.5

 114 to 265

15

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

1/4 of sum of diameters of two adjacent tanks

256 to 341

15

30

341 to 454

15

38

454 to 757

15

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

  757 to 3785

15

91

  3785 or greater

15

122

NOTES: Abovementioned distances are measured from the outside edge of an aboveground tank or from the filling connection or the relief valve of an underground or mounded tank.

6.11. Separation distances may be reduced by the provision of a fire wall in accordance with the following rules:

The minimum distance between the tank and the fire wall is 1.5 m.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

A = A + B (m)

Where:

D: minimum separation distance indicated in Table 1;

A: distance measured horizontally from the tank to the gable of the fire wall;

B: distance measured horizontally from the above-determined gable of the fire wall to the adjacent structure (housing or office building, etc.)

Figure 1. Separation distance from a tank with a fire wall

6.12. Fire walls are normally used on one side of a tank or tank grouping.  Fire walls should not be used on more than two sides of tank grouping or where the ventilation would be impaired.

6.13. LPG tanks and oxygen containers must be sited according to the separation distances in Table 2.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

Capacity of liquid oxygen container (m3)

 

Capacity of LPG tank (m3)

 

Separation distance (m)

Up to 125 m3

Up to 2.5 m3

6

 

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

7,5

 

9.0 m3 or above

15

125 m3 or above

Up to 5.0 m3

30

 

5.0 m3 or above

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

The adjacent ends of the cylindrical tanks designed for horizontal installation shall be separated from each other in a row; they must be installed parallel with ends in line and must not be directed toward housing or service buildings. Aboveground tanks shall be installed in groups. The number of tanks in one group depends on the fire protection system and is provided for in Table 3.

Table 3 – Maximum number of aboveground tanks in one group

Fire protection provided by

Maximum number of tanks in one group (tanks)

Minimum separation distances between groups (m)

 

Hose streams and delivery hoses

6

15

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

6

7.6

Fixed water spray

9

7.6

Tank with insulation capable of limiting the tank temperature to not over 427 °C for a minimum of 50 minutes.

9

7.6

6.15. Separation distances from LPG filling facilities to adjacent buildings and to LPG tanks are provided for in Table 4.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

Adjacent buildings

Separation distance (m)

Out-of-control area, fixed sources of ignition, road and rail points of LPG transfer

15

Aboveground tank of less than 9 m3

7.5

Aboveground tank of 9 m3 to 140 m3

10

Aboveground tank of 140 m3 or above

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

Tank valves and appurtenances above the grade of underground tanks or mounded tanks of:

 

Up to 2.5 m3

5

 2.5 m3 to 140 m3

7.5

140 m3 to 350 m3

11

350 m3 or above

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

6.16. Separation distances between points of LPG transfer by road or rail tankers and adjacent buildings are provided for in Table 5.  

Table 5 - Separation distances between points of LPG transfer and adjacent buildings

Adjacent buildings

Separation distance (m)

Homes or buildings with fire walls

3.1

Homes or buildings with other than fire walls

7.6

Building wall openings or pits at or below the level of the point of transfer

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

Line of adjoining property that can be built upon

7.6

Outdoor places of public assembly including athletic fields, and play-grounds

15

Public streets

7.6

Mainline railroad track centerlines

7.6

Aboveground LPG tanks of 16 m3 to 25 m3

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

Aboveground LPG tanks of 25 m3 to 125 m3

6

Aboveground LPG tanks of 125 m3 or above

9

6.17. Underground tanks must be protected from external loads on the tank shell, including loads from cars and other vehicles, etc.

6.18. Pumps and compressors shall not be located beneath tanks.

6.19. Vaporizing equipment of any types shall not be installed within the minimum separation distance of 1.5 m from the outer edge of the tank. Vaporizing equipment must be installed within a suitable electrical safety zone or to keep a regulated distance to the fixed ignition source.

7. Corrosion control

7.1. Each tank shall be protected against corrosion. Protective coatings must be tested for protection of tanks from the effects of corrosion at periodical intervals not exceeding 2 years.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

7.3. Fireproofting covering of a tank shall be tested at periodical intervals not exceeding 05 years which are same as those for testing for wall and shell thickness as well as inspection of inner side of a tank.

8. Labeling

A label must indicate the following information:

- Name of manufacturer;

- Date of manufacture;

- Manufacturing standard;

- Maximum allowable operating pressure;

- Minimum allowable operating pressure;

- Minimum operating temperature;

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản TCVN

- Inspecting agency.

 

LIST OF REFERENCED DOCUMENTS

1) NFPA 58 : 2001 Liquefied Petroleum Gas Code.

2) AS 1596 - 1989 LP Gas - Storage and Handling / Australian Standard.

3) API 2510 - 2001 : Design and Construction of LPG Installations.

25
Tiện ích dành riêng cho tài khoản TVPL Basic và TVPL Pro
Tiện ích dành riêng cho tài khoản TVPL Basic và TVPL Pro
Tiện ích dành riêng cho tài khoản TVPL Basic và TVPL Pro
Tải về National Standard TCVN 6486:2008 for Liquefied petroleum gas ("LPG") - Pressurised storage - Requirements for design and location of installation
Tải văn bản gốc National Standard TCVN 6486:2008 for Liquefied petroleum gas ("LPG") - Pressurised storage - Requirements for design and location of installation

Dung tích của một bồn chứa m3

Khoảng cách an toàn tối thiểu

m

 

Bồn đặt chính hoặc đắp đất

Bồn đặt nổi

Khoảng cách giữa các bồn

<0,5

3

1,5

0

Từ 0,5 đến dưới 1,0

3

3

0

Từ 1,0 đến dưới 1,9

3

3

1

Từ 1,9 đến dưới 7,6

3

7,6

1

Từ 7,6 đến dưới 114

15

15

1,5

Từ 114 đến dưới 265

15

23

1/4 tổng đường kính hai bồn lân cận

Từ 256 đến dưới 341

15

30

Từ 341 đến dưới 454

15

38

Từ 454 đến dưới 757

15

61

Từ 757 đến dưới 3785

15

91

Từ 3785 tr lên

15

122

CHÚ THÍCH: Khoảng cách trên được tính từ mép bồn chứa nổi và tính từ cụm van xuất nhập, họng xả van an toàn đối với bồn đặt chìm hoặc đắp đất.

6.11. Khi sử dụng giải pháp giảm khoảng cách an toàn bằng tường ngăn cháy thì phải tuân thủ theo nguyên tắc sau:

Khoảng cách tối thiểu từ bồn đến tường ngăn cháy là 1,5 m.

Khoảng cách an toàn khi có tường ngăn cháy sẽ được tính theo công thức:

D = A + B (m)

Trong đó:

D là khoảng cách an toàn tối thiểu quy định ở Bảng 1;

A là khoảng cách nằm ngang từ thân bồn chứa đến đầu hồi tường ngăn cháy;

B là khoảng cách nằm ngang từ đầu hồi tường ngăn cháy xác định ở trên đến công trình lân cận (nhà, văn phòng ...).

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

Hình 1 - Cách tính khoảng cách an toàn từ bồn chứa khi có tường ngăn cháy

6.12. Tường ngăn cháy thường đặt cạnh bồn hoặc nhóm bồn. Không sử dụng tường ngăn cháy quá hai cạnh khu bồn hoặc tại nơi làm suy yếu khả năng thông gió khu vực đặt bồn.

6.13. Khoảng cách an toàn giữa bồn chứa LPG đến bồn chứa ôxy quy định tại Bảng 2 .

Bảng 2 - Khoảng cách an toàn từ bồn chứa LPG tới bồn ôxy lỏng

Dung tích bồn chứa oxy lỏng

m3

Dung tích bồn chứa LPG

m3

Khoảng cách an toàn

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

Đến dưới 125 m3

Dưới 2,5 m3

6

 

Từ 2,5 m3 đến dưới 9,0 m3

7,5

 

Từ 9,0 m3 tr lên

15

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

Dưới 5,0 m3

30

 

Từ 5,0 m3 tr lên

45

Các bồn chứa hình trụ nằm ngang không được đặt nối đuôi nhau và không được đặt thẳng hàng theo một trục dọc, hướng về phía nhà ở hoặc các công trình dịch vụ. Các bồn chứa nổi b trí thành từng cụm, số lượng trong một cụm phụ thuộc vào kiểu hệ thống phòng cháy chữa cháy và được quy định theo Bảng 3.

Bảng 3 – S lượng bồn chứa nổi tối đa trong một cụm

Thiết bị h thống phòng cháy chữa cháy cho bồn chứa

Số lượng bồn chứa tối đa trong một cụm

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

Khoảng cách tối thiểu giữa các cụm bốn chứa

m

Họng lấy nước và cuộn ống mềm

6

15

Lăng giá phun nước kiểu cố định

6

7,6

Hệ thống dàn phun sương lắp cố định

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

7,6

Bồn có lớp cách nhiệt giữ nhiệt độ bồn chứa không quá 427 °C và có độ bn chịu nhiệt đến 50 min.

9

7,6

6.15. Khoảng cách an toàn từ nhà đóng nạp bình LPG đến công trình lân cận và đến bồn chứa quy định tại Bảng 4.

Bảng 4 - Khoảng cách an toàn từ nhà đóng nạp bình LPG đến công trình lân cận đến bồn chứa

Công trình lân cận

Khoảng cách an toàn

m

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

15

Bồn nổi dung tích dưới 9 m3

7,5

Bồn nổi dung tích từ 9 m3 đến dưới 140 m3

10

Bồn nổi dung tích từ 140 m3 trở lên

15

Hệ thống van, phụ kiện nổi bên ngoài của bồn đặt chìm hoặc đắp đất có sức chứa :

 

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

5

Từ 2,5 m3 đến dưới 140 m3

7,5

Từ 140 m3 đến dưới 350 m3

11

Từ 350 m3 trở lên

15

6.16. Khoảng cách an toàn giữa điểm xuất nhập LPG bằng xe bồn vận chuyển hoặc toa bồn đường sắt tới các công trình lân cận được quy định tại Bảng 5.

Bảng 5 - Khoảng cách an toàn giữa điểm xuất nhập LPG và các công trình lân cận

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

Khoảng cách an toàn

m

Nhà hoặc công trình xây dựng có tường ngăn cháy

3,1

Nhà hoặc công trình xây dựng không có tường ngăn cháy

7,6

Các kết cấu h của tường nhà, hào rãnh vị trí ngang hoặc thấp hơn cao độ điểm xuất nhập

7,6

Ranh giới công trình lân cận được quy hoạch

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

Nơi công cộng tập trung đông người, sân chơi, sân thể thao ngoài trời

15

Đường phố

7,6

Trục tim đường sắt

7,6

Bồn chứa LPG nổi có sức chứa 16 m3 đến dưới 25 m3

3

Bồn chứa LPG nổi có sức chứa 25 m3 đến dưới 125 m3

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

Bồn chứa LPG nổi có sức chứa từ 125 m3 trở lên

9

6.17. Các bồn chứa ngầm phải được bảo vệ để tránh tác động của các tải trọng bên ngoài lên vỏ bồn chứa như: ô tô, các phương tiện chuyển động,...

6.18. Bơm và máy nén không được để ngay phía dưới bồn.

6.19. Trong khoảng cách an toàn 1,5 m từ mép bồn chứa không được bố trí thiết bị hóa hơi thuộc bất kỳ loại nào. Thiết bị hóa hơi phải được bố trí trong vùng an toàn điện phù hợp hoặc khoảng cách tới ngọn lửa cố định theo đúng quy định.

7. Chống ăn mòn

7.1. Tất cả các bồn chứa phải được bảo vệ chống ăn mòn. Lớp phủ bảo vệ phải kiểm tra hai năm/lần để tránh hiện tượng ăn mòn có hại cho bồn chứa.

7.2. Không được sử dụng lớp phủ chống cháy thay thế hoặc hỗ trợ cho việc chữa cháy bằng nước trừ khi lớp phủ này cho phép kiểm tra bên trong và đo chiều dày của vỏ bồn và phải được sự đồng ý của cơ quan có thẩm quyền.

7.3. Các bồn chứa sử dụng lớp phủ chống cháy phải tuân thủ thời hạn kiểm tra độ dày thành vỏ bồn và kiểm tra bên trong ít nhất 5 năm/lần.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

Các thông tin dưới đây phải ghi trên nhãn:

- Tên nhà chế tạo ;

- Tháng năm chế tạo ;

- Tiêu chuẩn chế tạo;

- Áp suất làm việc cao nhất;

- Áp suất làm việc thấp nhất;

- Nhiệt độ làm việc thấp nhất;

- Dung tích nước;

- Cơ quan kiểm tra.

...

...

...

Bạn phải đăng nhập tài khoản TVPL Pro để xem được toàn bộ nội dung văn bản Tiếng Anh

THƯ MỤC TÀI LIỆU THAM KHẢO

1) NFPA 58 : 2001 Liquefied Petroleum Gas Code (Quy phạm về Khí dầu mỏ hóa lỏng).

2) AS 1596 - 1989 LP Gas - Storage and Handling / Australian Standard (Khí dầu mỏ hóa lỏng – Tn chứa và vận chuyển ).

3) API 2510 - 2001 : Design and Construction of LPG Installations (Thiết kế và xây dựng công trình LPG)

Văn bản được hướng dẫn - [0]
[...]
Văn bản được hợp nhất - [0]
[...]
Văn bản bị sửa đổi bổ sung - [0]
[...]
Văn bản bị đính chính - [0]
[...]
Văn bản bị thay thế - [0]
[...]
Văn bản được dẫn chiếu - [0]
[...]
Văn bản được căn cứ - [0]
[...]
Văn bản liên quan ngôn ngữ - [1]
[...]
Văn bản đang xem
National Standard TCVN 6486:2008 for Liquefied petroleum gas ("LPG") - Pressurised storage - Requirements for design and location of installation
Số hiệu: TCVN6486:2008
Loại văn bản: Tiêu chuẩn Việt Nam
Lĩnh vực, ngành: Công nghiệp
Nơi ban hành: ***
Người ký: ***
Ngày ban hành: 01/01/2008
Ngày hiệu lực: Đã biết
Ngày đăng: Đã biết
Số công báo: Đã biết
Tình trạng: Đã biết
Văn bản liên quan cùng nội dung - [0]
[...]
Văn bản hướng dẫn - [0]
[...]
Văn bản hợp nhất - [0]
[...]
Văn bản sửa đổi bổ sung - [0]
[...]
Văn bản đính chính - [0]
[...]
Văn bản thay thế - [0]
[...]
[...] Đăng nhập tài khoản TVPL Basic hoặc TVPL Pro để xem toàn bộ lược đồ văn bản